Power supply: switched-mode; for DIN rail; 135.6W; 12VDC; 11.3A

45.09/ gab.Цена
в том числе НДС 21%
ID:258819
Код:HDR-150-12
Артикул:HDR-150-12
Группа:Электроника и промышленностьEnerģijas avoti (LV)Barošanas avoti (LV)Barošanas avoti DIN sliedei (LV)
Производитель:MEAN WELL
Доступно на складе:
1- Precizēt pieejamību rakstot uz e-pastu semicom@semicom.lv
Время доставки:4-6дней
Описание товара


ultra slim design with 105 mm (6SU) width

universal input 85 ~ 264 VAC (277 VAC operational)

no load power consumption isolation class II

DC output voltage adjustable

protections: short circuit / overload / over voltage

cooling by free air convection

DIN rail TS-35/7.5 or 15 mountable

over voltage category III

LED indicator for power on

3 years warranty

applications:

household control system

building automation

industrial control system

factory automation

electro-mechanical apparatus

[b]for professional use only[/b]

This device must be installed by a qualified person.

output:

DC voltage: 12 V

rated current:

115 VAC (rated current): 10.2 A

230 VAC (rated current): 11.3 A

rated power:

115 VAC (rated power): 122.4 W

230 VAC (rated power): 135.6 W

ripple & noise (max.): 100 mVp-p

voltage adj. range: 10.8 - 13.8 V

voltage tolerance: ± 2.0 %

line regulation: ± 1.0 %

load regulation: ± 1.0 %

setup, rise time: 500 ms, 60 ms / 230 VAC - 500 ms, 60 ms / 115 VAC at full load

hold up time (typ.): 30 ms / 230 VAC - 12 ms / 115 VAC at full load

input:

voltage range: 85-264 VAC (277 VAC operational) - 120-370 VDC (390 VDC operational)

frequency range: 47 - 63 Hz

efficiency (typ.): 89 %

ac current (typ.): 3 A / 115 VAC - 70 A / 230 VAC

inrush current (typ.): cold start 35 A / 115 VAC - 70 A / 230 VAC

protection:

overload:

105 - 135 % rated output power

protection type: constant current limiting withing 50% ~ 100% rated output voltage, recovers automatically after fault condition is removed

hiccup mode when output voltage overvoltage:

14.2 ~ 16.2 V

protection type: shut down output voltage, re-power on to recover

environment:

working temperature: -30 to +70 °C

working humidity: 20 to 90 % RH non-condensing

storage: -40 to +85 °C, 10 to 95% RH non-condensing

temperature coefficient: ± 0.03 %/°C (0 - 45°C ) RH non-condensing

vibration: 10 - 500 Hz, 2G 10 min / 1 cycle, 60 min each along X, Y, Z axes; mounting: compliance to IEC60068-2-6

operating altitude: 2000 m

over voltage category: III, according to EN62368, EN61558, EN50178, EN60664-1, EN62477-1, altitude up to 2000 meters

safety & EMC:

safety standards: IEC62368-1, UL62368-1, UL61010, TUV EN61558-2-16, EACTPTC004 approved; design refer to EN50178, TUV EN62368-1

withstand voltage: input to output: 4 kVAC

isolation resistance: input to output: 100 MOhm / 500 VDC / 25 °C / 70 % RH

EMC emission:

conducted (EMC emission): EN55032 (CISPR32) / Class B

radiated: EN55032 (CISPR32) / Class B

harmonic current: EN61000-3-2 / Class A

voltage flicker: EN61000-3-3

EMC immunity:

ESD: EN61000-4-2 / Level 3, 8KV air - Level 2, 4KV contact - criteria A

radiated susceptibility: EN61000-4-3 / Level 3 - criteria A

EFT/Burest: EN61000-4-4 / Level 3 - criteria A

surge: EN61000-4-5 / Level 4, 2KV/L-N - criteria A

conducted (EMC immunity): EN61000-4-6 / Level 3 - criteria A

magnetic field: EN61000-4-8 / Level 4, criteria A

voltage dips and interruptions: EN61000-4-11 / >95% dip 0.5 periods, 30% dip 25 periods - >95% interruptions 250 periods

other:

MTBF: 536 hrs min. MIL-HDBK-217F (25 °C)

dimensions: 105 x 90 x 54.5 mm (W x H x D)