ultra slim design with 35 mm (2SU) width

universal input 85-264 VAC (277 VAC operational)

no load power consumption isolation class II

pass LPS (limited power source)

DC output voltage adjustable

protections: short circuit / overload / over voltage

cooling by free air convection (working temperature : -30 - +70°C)

DIN rail TS-35/7.5 or 15 mountable

over voltage category III

LED indicator power on

3 year warranty

[b]for professional use only[/b]

This device must be installed by a qualified person.

output:

DC voltage: 5 V

rated current: 3 A

current range: 0 - 3 A

rated power: 15 W

ripple & noise (max.): 80 mVp-p

voltage adj. range: 4.5 - 5.5 V

voltage tolerance: ± 2.0 %

line regulation: ± 1.0 %

load regulation: ± 1.0 %

setup, rise time: 500 ms, 50 ms / 230 VAC - 500 ms, 50 ms / 115 VAC at full load

hold up time (typ.): 30 ms / 230 VAC - 12 ms / 115 VAC at full load

input:

voltage range: 85-264 VAC (277 VAC operational) - 120-370 VDC (390 VDC operational)

frequency range: 47 - 63 Hz

efficiency (typ.): 82 %

ac current (typ.): 0.88 A / 115 VAC - 0.48 A / 230 VAC

inrush current (typ.): cold start 25 A / 115 VAC - 45 A / 230 VAC

protection:

overload:

105 - 160 % rated output power

protection type: constant current limiting, recovers automatically after fault condition is removed

overvoltage:

5.75 - 7.5 V

protection type: shut down output voltage, re-power on to recover

environment:

working temperature: -30 to +70 °C

working humidity: 20 to 90 % RH non-condensing

storage: -40 to +85 °C, 10 to 95 % RH

temperature coefficient: ± 0.03 %/°C (0 - 50 °C )

vibration: 10 - 500 Hz, 2G 10 min / 1 cycle, 60 min each along X, Y, Z axes; mounting: compliance to IEC60068-2-6

operating altitude: 2000 m

over voltage category: III, according to EN61558, EN50178, EN60664-1, EN62477-1, altitude up to 2000 meters

safety & EMC:

safety standards: UL60950-1, UL508, TUV EN61558-2-16, IEC60950-1 approved, design refer to TUV EN60950-1

withstand voltage: input to output: 4 kVAC

isolation resistance: input to output: 100 MOhm / 500 VDC / 25 °C / 70 % RH

EMC emission:

conducted (EMC emission): EN55032 (CISPR32) / Class B

radiated: EN55032 (CISPR32) / Class B

harmonic current: EN61000-3-2 / Class A

voltage flicker: EN61000-3-3

EMC immunity:

ESD: EN61000-4-2 / Level 3, 8KV air - Level 2, 4KV contact - criteria A

radiated susceptibility: EN61000-4-3 / Level 3 - criteria A

EFT/Burest: EN61000-4-4 / Level 3 - criteria A

surge: EN61000-4-5 / Level 4, 2KV/L-N - criteria A

conducted (EMC immunity): EN61000-4-6 / Level 3 - criteria A

magnetic field: EN61000-4-8 / Level 4, criteria A

voltage dips and interruptions: EN61000-4-11 / >95% dip 0.5 periods, 30% dip 25 periods - >95% interruptions 250 periods

other:

MTBF: 968.1Kh, MIL-HDBK-217F (25 °C)